XM3.1-915-HP
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM3.1-915-HP
Firmware V1.01.0
Major Alarm OK
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 122.71 V
Current 5.12 A
Power 530 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 3,000 Wh
Output
Voltage 62.17 V
Power 420 W
Apparent Power 460.67 VA
Frequency 60.03 Hz
Percent Load 49.40 %
Output Setting 60 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 7.41 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Disable
Total Standby Events 126
Time Since Last Standby Event 145d 21h:42m
Time in Last Standby Event 0d 1h:19m
Total Time in Standby 1,011 min
Standby Events Since Reset 57
Time in Standby Since Reset 530 min
Time Since Reset 1,269 day(s)
Total Run Time 1,269 day(s)
Transformer Run Time 1,269 day(s)
Total Downtime 0d 10h:07m
Oil Cap Lifespan Consumed 53.3 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 24 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 